Nomographs for H2O-LiBr absorption-panel cooling systems

 
δείτε την πρωτότυπη σελίδα τεκμηρίου
στον ιστότοπο του αποθετηρίου του φορέα για περισσότερες πληροφορίες και για να δείτε όλα τα ψηφιακά αρχεία του τεκμηρίου*
κοινοποιήστε το τεκμήριο



Nomographs for H2O-LiBr absorption-panel cooling systems (EN)

Rogdakis, ED (EN)

N/A (EN)

Panel cooling of buildings offers energy savings over conventional space-cooling systems. We present a procedure for calculating the performance of H2O-LiBr absorption-panel cooling systems, in which the evaporator is the panel itself. Nomographs have been developed for this approach. Under the conditions examined, the H2O-LiBr absorption unit operates with a theoretical performance coefficient of about 90% and with a practically constant specific cooling capacity of 2394 kJ/kg H2O. For common values of the parameters involved, the panel cooling power varies from 25 to 175 W/m2 and the cooling water mass-flow rate through the panel is 40-260 g/m2h. The thermal power needed to drive the system varies from 27 to 200 W/m2 and the associated temperatures from 70 to 100 °C; thus, the system may be operated on solar energy. © 1992. (EN)

journalArticle

Water (EN)
Cooling Systems (EN)
Lithium Compounds (EN)
Absorption Panel Cooling Systems (EN)
Nomograms (EN)
Structural Panels (EN)
Performance (EN)
Mathematical Models (EN)

Εθνικό Μετσόβιο Πολυτεχνείο (EL)
National Technical University of Athens (EN)

Energy (EN)

1992


PERGAMON-ELSEVIER SCIENCE LTD (EN)